Notifications
You must be signed in to change notification settings - Fork 131
Items EIB_Items
See original
None
EIB (European Installation Bus) items.
EIB/KNX website: http://konnex.org
The following EIB types are supported: (MH Klassname, DPT Type, EIS Type, Description)
EIB1: DPT 1.001, EIS 1, Switches
EIB2: NA, EIS 2, Dimmers
EIB3: DPT 10.000, EIS 3, Time
EIB4: DPT 11.000, EIS 4, Date
EIB5: DPT 9.000, EIS 5, Values (weather stations etc)
EIB6: DPT 5.001, EIS 6, Scaling (0 - 100%)
EIB7: NA, EIS 7, Motor drives
EIB8: DPT 2.001, EIS 8, forced control 2 bit
EIB9: DPT 14.00x, EIS 9, 32-bit float
EIB10: DPT 7.001, EIS 10, 16-bit unsigned integer
EIB10_1: DPT 8.001, EIS 10.001, 16-bit signed integer
EIB11: DPT 12.001, EIS 11, 32-bit unsigned integer
EIB11_1: DPT 13.001, EIS 11.001, 32-bit signed integer
EIB14: DPT 6.001, EIS 14, 8-bit signed integer
EIB14_1: DPT 5.010, EIS 14.1; 8-bit unsigned integer
EIB15: DPT 16.000, EIS 15, 14 byte text messages
EIBW: NA, NA, summary object for 2 EIS1 Objects
to define the state of a window
(closed, tilt, open)
Method | Description |
---|---|
eib_items_by_id |
Lookup EIB_Item with the given address |
new |
Generic EIB_Item class. This class is not instantiated directly. It is used to inherit common EIB properties |
printname |
Item name to appear in logs etc |
set_receive |
detected an EIB event on the bus. Update item state to reflect the value in the event ! |
send_write_msg |
generate EIB message to set a value |
send_read_msg |
generate EIB message to read a value |
receive_write_msg |
process a message to set a value |
receive_reply_msg |
process a message with a reply value (read response) |
receive_msg |
entry point from device interface. Analyse message and call appropriate receive_*_msg handler |
start_read_timer |
set a timeout for waiting for read response |
stop_read_timer |
disable timer |
read_timeout |
No reply to read request. Retry or give up. |
read_request |
send a read request, and start timer |
delayed_read_request |
wait a while and then send a read request. If a read request is sent too soon, the EIB actuator may not have obtained a stable value, so we want to delay before sending the request. |
None
09/09/2005 Created by Peter Sjödin [email protected] 06/01/2009 Enhanced by Ralf Klueber r(at)lf-klueber.de 08/01/2009 Listening addresses by Mike Pieper [email protected]
None
Method | Description |
---|---|
decode |
translate EIS 1 data to state (on/off) |
encode |
translate state to EIS 1 data |
A group of EIB1 items. Setting the value of an EIB1 group will affect all members in the group. The class is used to keep track of EIB1 group memberships. If a write message is detected, all members will be updated.
EIS 2: Dimming EIB dimmers can be controlled in three different ways:
- "control": brighten, dim, stop. Handled by class EIB21_Item
- "value": numerical value: Handled by class EIB6_Item
- "position": on, off. Handled by class EIB1_Item
Class EIB2_Item is a meta-item to represent dimmers, consist of the three underlying item. The main purpose is to make a dimmer appear as a single item, while the real work is done by the three underlying items.
The identifier for the EIB2_Item is composed of the concatenation of the addresses of the three underlying items, with '|' between them. For example, '1/0/90|1/0/91|1/4/1' is a dimmer with control address 1/0/90, value address 1/0/91, and position address 1/4/1.
Method | Description |
---|---|
new |
create an EIB2_Item. Instantiate the three underlying items. |
position |
return "position" sub-item |
control |
return "control" sub-item |
value |
return "value" sub-item |
set |
Set EIB2 item. Parse state to determine the corresponding sub-item to call. |
set_receive |
received an event from one of the sub_items. If it was a numerical value ("Value"), update the "Position" subitem to 'on' or 'off'. If the value was zero, also set self to 'off'. Update level (0-100) to represent dimmer position |
state_level |
return 'on', 'off' or 'dim', depending on current setting (as obtained from "value" sub-item) |
A generic class for the three dimming sub-functions
Method | Description |
---|---|
`dimmer`` | return "dimmer" meta-item |
set_receive |
forward to meta-item |
Dimming sub-function "control"
Method | Description |
---|---|
immer_timeout |
dimmer should have reached stable state. Issue a read request to obtain current value |
set |
To allow adjusting dimmer value in real-time from for example web interface: If state is set to same dim/brighten value twice before dimmer timer has expired, it means "stop". For example, first 'dim' means start dimming, second means stop dimming (This behaviour is configurable via configuration parameter "eib_dim_stop_on_repeat" ) |
set_receive |
if it is a 'stop' event, generate a read request for the 'Value' sub-item, to learn the actual dimmer setting |
Dimming sub-function "value". Set dimmer to a given brightness level (0-100) with 8 bit resolution Values are coded according to EIS 6
Method | Description |
---|---|
set_receive |
detected a "read" or "write" message on the bus. For readable actuators, don't trust the values in "write" messages, as they may not have been accepted by the actuator. So if it is a write, and the actuator is readable, generate a read request to obtain the actual value from the actuator |
Dimming sub-function "position". Set dimmer to on/off. Values are coded according to EIS 1
Time
Time
"scaling". Relative values 0-100% with 8 bit resolution
Method | Description |
---|---|
set_receive |
detected a "read" or "write" message on the bus. For readable actuators, don't trust the values in "write" messages, as they may not have been accepted by the actuator. So if it is a write, and the actuator is readable, generate a read request to obtain the actual value from the actuator |
"forced control". 2 bit
Enforcement ON + Turn Device ON (11)
Enforcement ON + Turn Device OFF (10)
Enforcement OFF + Turn Device OFF (00)
Enforcement OFF + Turn Device ON (01)
32-bit float
16-bit unsigned integer
16-bit signed integer
32-bit unsigned integer
32-bit signed integer
8-bit signed integer
"scaling". Relative values 0-255 with 8 bit resolution
Method | Description |
---|---|
set_receive |
detected a "read" or "write" message on the bus. For readable actuators, don't trust the values in "write" messages, as they may not have been accepted by the actuator. So if it is a write, and the actuator is readable, generate a read request to obtain the actual value from the actuator |
Drive control
Blinds, windows, etc
Drives can be controlled in two different ways:
1. "move": up/down
2. "stop": stop/step movement
NB EIS7 objects may not be read, since this can cause drive movements
Method | Description |
---|---|
set |
set EIB drive item. Parse state to determine the corresponding sub-item to call. Don't modify own state here -- that will be done later, when/if the sub-items call set_receive for this item. |
Generic class for drive sub-functions
Method | Description |
---|---|
new |
Instantiated with last args "driveid" the id of EIS7 item to which this subitem belongs |
set_receive |
forward to main Drive item (EIS7 item) |
Dimming sub-function "move"
Drive sub-function "stop"
Drive sub-function "step-up/step-down"
14-Byte Text Message
EIBW: Windows type of object wich uses 2 underlaying EIB1 Items (Top and Bottom) Definition as follows EIBW , GA1|GA2, Name, nameforOffOf|nameOffOn|NameOnOff|NameOnOn
Method | Description |
---|---|
new |
create an EIBW_Item. Instantiate the three underlying items. |
set_receive |
received an event from one of the sub_items. |
Generic class for the three dimming sub-functions
Method | Description |
---|---|
set_receive |
forward to meta-item |
09/09/2005 Created by Peter Sjödin [email protected] 06/01/2009 Enhanced by Ralf Klueber r(at)lf-klueber.de 08/01/2009 Listening addresses by Mike Pieper [email protected]
None