Skip to content

Commit

Permalink
[danfossairunit] Add filter period channel (openhab#11371)
Browse files Browse the repository at this point in the history
* Add filter period channel.

Fixes openhab#11310

Signed-off-by: Jacob Laursen <[email protected]>

* Round remaining filter life percentage to one decimal.

Signed-off-by: Jacob Laursen <[email protected]>

* Improve and extend example configuration.

Signed-off-by: Jacob Laursen <[email protected]>

* Mark filter period channel as advanced due to Link CC/Air Dial conflicts.

Signed-off-by: Jacob Laursen <[email protected]>

* Add comment about value getting overwritten.

Signed-off-by: Jacob Laursen <[email protected]>

* Remove redundant parentheses.

Signed-off-by: Jacob Laursen <[email protected]>

* Fix SCA report: First javadoc author should have 'Initial contribution' contribution description.

Signed-off-by: Jacob Laursen <[email protected]>

* Fix SCA issue: NoEmptyLineSeparatorCheck

Signed-off-by: Jacob Laursen <[email protected]>
  • Loading branch information
jlaur authored and Nemer_Daud committed Jan 28, 2022
1 parent 5f6ca7c commit e0967d7
Show file tree
Hide file tree
Showing 8 changed files with 79 additions and 18 deletions.
51 changes: 39 additions & 12 deletions bundles/org.openhab.binding.danfossairunit/README.md
Original file line number Diff line number Diff line change
Expand Up @@ -41,6 +41,7 @@ These are the available configuration parameters:
| exhaust_temp | recuperator | Number | RO | Temperature of the air when pushed outside |
| battery_life | service | Number | RO | Remaining Air Dial Battery Level (percentage) |
| filter_life | service | Number | RO | Remaining life of filter until exchange is necessary (percentage) |
| filter_period | service | Number | RW | Number of months between filter replacements (between 3 and 12). This value affects calculation of filter_life by the unit, and might get overwritten by Air Dial or Link CC Controller. |


## Full Example
Expand All @@ -63,21 +64,47 @@ updateUnchangedValuesEveryMillis=30000]
### Items

```
Dimmer Lueftung_Drehzahl_Manuell "Drehzahl Lüftung %" (All,Lueftung) {channel = "danfossairunit:airunit:myairunit:main#manual_fan_speed"}
Number Lueftung_Drehzahl_Supply "Drehzahl Lüftung Zuluft (rpm)" (All,Lueftung) {channel = "danfossairunit:airunit:myairunit:main#supply_fan_speed"}
Number Lueftung_Drehzahl_Extract "Drehzahl Lüftung Abluft (rpm)" (All,Lueftung) {channel = "danfossairunit:airunit:myairunit:main#extract_fan_speed"}
String Lueftung_Mode "Betriebsart Lüftung" (All,Lueftung) {channel = "danfossairunit:airunit:myairunit:main#mode"}
Switch Lueftung_Boost "Stoßlüftung" (All,Lueftung) {channel = "danfossairunit:airunit:myairunit:main#boost"}
Switch Lueftung_Bypass "Lüftung Bypass" (All,Lueftung) {channel = "danfossairunit:airunit:myairunit:recuperator#bypass"}
Dimmer DanfossHRV_ManualFanStep "Manual Fan Step [%s]" {channel = "danfossairunit:airunit:myairunit:main#manual_fan_step"}
Number DanfossHRV_SupplyFanSpeed "Supply Fan Speed" {channel = "danfossairunit:airunit:myairunit:main#supply_fan_speed"}
Number DanfossHRV_ExtractFanSpeed "Extract Fan Speed" {channel = "danfossairunit:airunit:myairunit:main#extract_fan_speed"}
String DanfossHRV_Mode "Operation Mode" {channel = "danfossairunit:airunit:myairunit:main#mode"}
Switch DanfossHRV_Boost "Boost" {channel = "danfossairunit:airunit:myairunit:main#boost"}
Switch DanfossHRV_Bypass "Bypass" {channel = "danfossairunit:airunit:myairunit:recuperator#bypass"}
Number:Dimensionless DanfossHRV_Humidity "Relative humidity" <humidity> { channel = "danfossairunit:airunit:myairunit:humidity#humidity" }
Number:Temperature DanfossHRV_RoomTemperature "Room air temperatuyre" <temperature> { channel = "danfossairunit:airunit:myairunit:temps#room_temp" }
Number:Temperature DanfossHRV_OutdoorTemperature "Outdoor air temperature" <temperature> { channel = "danfossairunit:airunit:myairunit:temps#outdoor_temp" }
Number:Temperature DanfossHRV_SupplyAirTemperature "Supply air temperature" <temperature> { channel = "danfossairunit:airunit:myairunit:recuperator#supply_temp" }
Number:Temperature DanfossHRV_ExtractAirTemperature "Extract air temperature" <temperature> { channel = "danfossairunit:airunit:myairunit:recuperator#extract_temp" }
Number:Temperature DanfossHRV_ExhaustAirTemperature "Exhaust air temperature" <temperature> { channel = "danfossairunit:airunit:myairunit:recuperator#exhaust_temp" }
Number DanfossHRV_RemainingFilterLife "Remaining filter life" { channel = "danfossairunit:airunit:myairunit:service#filter_life" }
Number DanfossHRV_FilterPeriod "Filter period" { channel = "danfossairunit:airunit:myairunit:service#filter_period" }
```

### Sitemap

```
Slider item=Lueftung_Drehzahl_Manuell
Text item=Lueftung_Drehzahl_Supply
Text item=Lueftung_Drehzahl_Extract
Selection item=Lueftung_Mode mappings=[DEMAND="Bedarfslüftung", OFF="Aus", PROGRAM="Programm", MANUAL="manuell"]
Switch item=Lueftung_Boost
Switch item=Lueftung_Bypass
sitemap danfoss label="Danfoss" {
Frame label="Control" {
Selection item=DanfossHRV_Mode mappings=[DEMAND="Demand", OFF="Off", PROGRAM="Program", MANUAL="Manual"]
Slider item=DanfossHRV_ManualFanStep step=10 visibility=[DanfossHRV_Mode=="MANUAL"]
Switch item=DanfossHRV_Bypass
Switch item=DanfossHRV_Boost
}
Frame label="Measurements" {
Text item=DanfossHRV_Humidity
Text item=DanfossHRV_RoomTemperature
Text item=DanfossHRV_OutdoorTemperature
Text item=DanfossHRV_SupplyAirTemperature
Text item=DanfossHRV_ExtractAirTemperature
Text item=DanfossHRV_ExhaustAirTemperature
}
Frame label="Fan" {
Text item=DanfossHRV_SupplyFanSpeed
Text item=DanfossHRV_ExtractFanSpeed
}
Frame label="Filter" {
Text item=DanfossHRV_RemainingFilterLife
Slider item=DanfossHRV_FilterPeriod minValue=3 maxValue=12
}
}
```
Original file line number Diff line number Diff line change
Expand Up @@ -59,7 +59,9 @@ public enum Channel {

// service channels
CHANNEL_BATTERY_LIFE("battery_life", ChannelGroup.SERVICE, DanfossAirUnit::getBatteryLife),
CHANNEL_FILTER_LIFE("filter_life", ChannelGroup.SERVICE, DanfossAirUnit::getFilterLife);
CHANNEL_FILTER_LIFE("filter_life", ChannelGroup.SERVICE, DanfossAirUnit::getFilterLife),
CHANNEL_FILTER_PERIOD("filter_period", ChannelGroup.SERVICE, DanfossAirUnit::getFilterPeriod,
DanfossAirUnit::setFilterPeriod);

private final String channelName;
private final ChannelGroup group;
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -57,6 +57,7 @@ public class Commands {
public static byte[] EXHAUST_TEMPERATURE = { 0x14, 0x75 };
public static byte[] BATTERY_LIFE = { 0x03, 0x0f };
public static byte[] FILTER_LIFE = { 0x14, 0x6a };
public static byte[] FILTER_PERIOD = { 0x14, 0x69 };
public static byte[] CURRENT_TIME = { 0x15, (byte) 0xe0 };
public static byte[] AWAY_TO = { 0x15, 0x20 };
public static byte[] AWAY_FROM = { 0x15, 0x21 };
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -19,7 +19,7 @@
/**
* This interface defines a communication controller that can be used to send requests to the Danfoss Air Unit.
*
* @author Jacob Laursen - Refactoring, bugfixes and enhancements
* @author Jacob Laursen - Initial contribution
*/
@NonNullByDefault
public interface CommunicationController {
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -213,7 +213,16 @@ public DecimalType getBatteryLife() throws IOException {
}

public DecimalType getFilterLife() throws IOException {
return new DecimalType(BigDecimal.valueOf(asPercentByte(getByte(REGISTER_1_READ, FILTER_LIFE))));
BigDecimal value = BigDecimal.valueOf(asPercentByte(getByte(REGISTER_1_READ, FILTER_LIFE)));
return new DecimalType(value.setScale(1, RoundingMode.HALF_UP));
}

public DecimalType getFilterPeriod() throws IOException {
return new DecimalType(BigDecimal.valueOf(getByte(REGISTER_1_READ, FILTER_PERIOD)));
}

public DecimalType setFilterPeriod(Command cmd) throws IOException {
return setNumberTypeRegister(cmd, FILTER_PERIOD);
}

public DateTimeType getCurrentTime() throws IOException, UnexpectedResponseValueException {
Expand All @@ -225,6 +234,14 @@ public PercentType setManualFanStep(Command cmd) throws IOException {
return setPercentTypeRegister(cmd, MANUAL_FAN_SPEED_STEP);
}

private DecimalType setNumberTypeRegister(Command cmd, byte[] register) throws IOException {
if (cmd instanceof DecimalType) {
byte value = (byte) ((DecimalType) cmd).intValue();
set(REGISTER_1_WRITE, register, value);
}
return new DecimalType(BigDecimal.valueOf(getByte(REGISTER_1_READ, register)));
}

private PercentType setPercentTypeRegister(Command cmd, byte[] register) throws IOException {
if (cmd instanceof PercentType) {
byte value = (byte) ((((PercentType) cmd).intValue() + 5) / 10);
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -80,7 +80,6 @@ private synchronized void discover() {
logger.debug("Try to discover all Danfoss Air CCM devices");

try (DatagramSocket socket = new DatagramSocket()) {

Enumeration<NetworkInterface> interfaces = NetworkInterface.getNetworkInterfaces();
while (interfaces.hasMoreElements()) {
NetworkInterface networkInterface = interfaces.nextElement();
Expand All @@ -96,7 +95,6 @@ private synchronized void discover() {
sendBroadcastToDiscoverThing(socket, interfaceAddress.getBroadcast());
}
}

} catch (IOException e) {
logger.debug("No Danfoss Air CCM device found. Diagnostic: {}", e.getMessage());
}
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -124,6 +124,7 @@
<label>Remaining Filter Life</label>
<description>Remaining life of filter until exchange is necessary</description>
</channel>
<channel id="filter_period" typeId="filterPeriod"/>
</channels>
</channel-group-type>

Expand Down Expand Up @@ -190,6 +191,12 @@
<category>Fan</category>
<state step="10" min="0" max="100" readOnly="true"/>
</channel-type>
<channel-type id="filterPeriod" advanced="true">
<item-type>Number</item-type>
<label>Filter Period</label>
<description>Number of months between filter replacements</description>
<state pattern="%d" min="3" max="12"/>
</channel-type>
<channel-type id="percentage">
<item-type>Number</item-type>
<label>Percentage</label>
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -23,6 +23,7 @@
import org.junit.jupiter.api.BeforeEach;
import org.junit.jupiter.api.Test;
import org.openhab.core.library.types.DateTimeType;
import org.openhab.core.library.types.DecimalType;
import org.openhab.core.library.types.OnOffType;
import org.openhab.core.library.types.PercentType;
import org.openhab.core.library.types.QuantityType;
Expand All @@ -31,7 +32,7 @@
/**
* This class provides test cases for {@link DanfossAirUnit}
*
* @author Jacob Laursen - Refactoring, bugfixes and enhancements
* @author Jacob Laursen - Initial contribution
*/
public class DanfossAirUnitTest extends JavaTest {

Expand Down Expand Up @@ -153,4 +154,12 @@ public void getManualFanStepWhenOutOfRangeThrows() throws IOException {
var airUnit = new DanfossAirUnit(communicationController);
assertThrows(UnexpectedResponseValueException.class, () -> airUnit.getManualFanStep());
}

@Test
public void getFilterLifeWhenNearestNeighborIsBelowRoundsDown() throws IOException {
byte[] response = new byte[] { (byte) 0xf0 };
when(this.communicationController.sendRobustRequest(REGISTER_1_READ, FILTER_LIFE)).thenReturn(response);
var airUnit = new DanfossAirUnit(communicationController);
assertEquals(new DecimalType("94.1"), airUnit.getFilterLife());
}
}