Chiller economizing using thermosiphon or fluid heat exchanger free cooling #10415
Chiller economizing using thermosiphon or fluid heat exchanger free cooling #10415
Conversation
### Integrated water-side economizer with air-cooled chiller ### | ||
|
||
Integrated water-side economizer with air-cooled chillers is likely possible with existing objects with minor additions to control of the water flow through the WWHX (HeatExchanger:FluidToFluid). One side of the WWHX would be connected to the supply side inlet node of the chiller evaporator (or other appropriate branch in the plant, i.e., pre-cool entire plant loop) while the other side of the WWHX would be connected to a demand side branch of the condenser loop. Activation of the condenser loop flow through the HX, to activate free cooling, would be accomplished through controls modification (2). The WWHX object already has inputs for Control Type, Heat Exchanger Setpoint Node Name, Minimum Temperature Difference to Activate Heat Exchanger, Operation Minimum Temperature Limit, and Operation Maximum Temperature Limit. I am unsure at this time which of these fields would be used for configuration as an integrated water-side economizer or if other inputs would be required. It may be as simple as adding a new Control Type = IntegratedWaterSideEconomizer to allow the proper controls. Investigation into the new control will include review of the Component Override Loop inputs (e.g., using chiller condenser inlet or evaporator outlet node temperature as a control point). | ||
|
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
I suspect you won't need to add a new control type to the WWHX. It can use a CoolingSetpoint* method. The chiller in series downstream is controlled by component setpoint based operation instead of load-based dispatch and should just pick up the modified temperatures.
CoolingSetpointOnOffWithComponentOverride is intended for the "all or nothing" parallel configuration. May need some testing.
|
||
``` | ||
HeatPump:PlantLoop:EIR:Cooling, | ||
A13, \field Refrigerant Migration Temperature Difference Curve Name |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
I sort of like the word Thermosiphon over Refrigerant Migration
…-Refrigerant-Migration-Decarbonization
…-Refrigerant-Migration-Decarbonization
@rraustad @Myoldmopar it has been 28 days since this pull request was last updated. |
2 similar comments
@rraustad @Myoldmopar it has been 28 days since this pull request was last updated. |
@rraustad @Myoldmopar it has been 28 days since this pull request was last updated. |
…-Refrigerant-Migration-Decarbonization
…-Refrigerant-Migration-Decarbonization
…-Refrigerant-Migration-Decarbonization
…-Refrigerant-Migration-Decarbonization
…-Refrigerant-Migration-Decarbonization
@@ -2464,6 +2462,9 @@ void ReformulatedEIRChillerSpecs::calculate(EnergyPlusData &state, Real64 &MyLoa | |||
|
|||
} // This is the end of the FlowLock Block | |||
|
|||
// set the module level variable used for reporting FRAC | |||
this->ChillerCyclingRatio = FRAC; | |||
|
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Unit tests showed this was not getting set correctly. Moved this equivalence outside the above IF block to capture the proper value regardless of FlowLock.
@@ -1528,6 +1528,7 @@ namespace PlantChillers { | |||
} // End of the Air Cooled/Evap Cooled Logic block | |||
|
|||
Real64 condInletTemp = state.dataLoopNodes->Node(this->CondInletNodeNum).Temp; | |||
this->CondInletTemp = condInletTemp; // needed if thermosiphon model is used |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
The new function uses this->CondInletTemp
in the calculation so need to set this before that new function is called.
if (this->thermosiphonDisabled(state)) { | ||
this->Power = FracFullLoadPower * FullLoadPowerRat * AvailChillerCap / this->COP * FRAC; | ||
} | ||
|
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Moved power calculation after where evap outlet temp is calculated.
@@ -3465,13 +3479,42 @@ TEST_F(EnergyPlusFixture, TestOperatingFlowRates_FullyAutosized_AirSource) | |||
|
|||
// call with run flag ON, flow locked at nonzero both | |||
state->dataPlnt->PlantLoop(1).LoopSide(DataPlant::LoopSideLocation::Supply).FlowLock = DataPlant::FlowLock::Locked; | |||
state->dataLoopNodes->Node(thisCoolingPLHP->loadSideNodes.inlet).MassFlowRate = 0.14; | |||
state->dataLoopNodes->Node(thisCoolingPLHP->loadSideNodes.inlet).MassFlowRate = 1.0; |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Updated to avoid -24 C evap outlet temp.
@@ -73581,17 +73581,30 @@ Chiller:Electric:EIR, | |||
\note PLR is the chilled water plant loop part load ratio (actual/design) | |||
\type object-list | |||
\object-list UnivariateFunctions | |||
A20, \field Temperature Difference Across Condenser Schedule Name | |||
A19, \field Temperature Difference Across Condenser Schedule Name |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Not sure why but the idd had a mismatch with alpha field numbers in several chiller models.
return true; | ||
} | ||
} | ||
|
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
There is an issue here with this new function being in 4 different places. It would be better to locate this function somewhere so that there would only be 1 new function. And variable names would need to be unified. I should check to see if I made a mistake in Chiller:Electric.
Real64 capFrac = this->ChillerPartLoadRatio * this->ChillerCyclingRatio; // Electric:EIR
Real64 capFrac = this->ChillerPartLoadRatio * this->ChillerCyclingRatio; // ReformulatedEIR
Real64 capFrac = this->CyclingRatio; // PlantChillers, Chiller:Electric
Real64 capFrac = this->partLoadRatio * this->cyclingRatio; // PlantLoopHeatPump:Cooling:EIR
UPDATE: Yes, it looks like Chiller:Electric needs to track both PLR and cycling ratio.
UPDATE: added partLoadRatio to Chiller:Electric and unified what these mean
Real64 capFrac = this->ChillerPartLoadRatio * this->ChillerCyclingRatio; // Electric:EIR
Real64 capFrac = this->ChillerPartLoadRatio * this->ChillerCyclingRatio; // ReformulatedEIR
Real64 capFrac = this->partLoadRatio * this->cyclingRatio; // PlantChillers, Chiller:Electric
Real64 capFrac = this->partLoadRatio * this->cyclingRatio; // PlantLoopHeatPump:Cooling:EIR
UPDATE 7/27: added thermosiphon model to COP chiller.
Real64 capFrac = this->partLoadRatio * this->cyclingRatio; // Chiller:ConstantCOP
Documenting previous diffs before partLoadRatio change to Chiller:Electric:
|
@@ -1913,6 +1926,7 @@ void ElectricEIRChillerSpecs::calculate(EnergyPlusData &state, Real64 &MyLoad, b | |||
|
|||
// If not air or evap cooled then set to the condenser node that is attached to a cooling tower | |||
Real64 condInletTemp = state.dataLoopNodes->Node(this->CondInletNodeNum).Temp; | |||
this->CondInletTemp = condInletTemp; // needed for thermosiphon model |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
If I revert (comment out) this change in the EIR and ReformulatedEIR chillers there are no eio or results diffs in example file ASHRAE901_Hospital_STD2019_Denver. This was verified through Binder plot results and diffing the eio files. The Binder script skips a plot if there are no diffs otherwise the script creates a plot.
This branch:
After revert of this line in 2 places:
Example diff from this branch for ASHRAE901_Hospital_STD2019_Denver:
format("Invalid Thermosiphon Capacity Fraction Curve Name = {}", | ||
thermosiphonTempCurveName.value().get<std::string>())); | ||
errorsFound = true; | ||
} |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Test severe error using PlantLoopHeatPump_EIR_LargeOffice-2-AWHP-AuxBoiler-Pri-Sec-4PipeBeam:
** Severe ** HeatPump:PlantLoop:EIR:Cooling ="AWHP_1 COOLING SIDE"
** ~~~ ** Invalid Thermosiphon Capacity Fraction Curve Name = ThermosiphonCurve2
** Severe ** HeatPump:PlantLoop:EIR:Cooling ="AWHP_2 COOLING SIDE"
** ~~~ ** Invalid Thermosiphon Capacity Fraction Curve Name = ThermosiphonCurve3
** Fatal ** Previous EIR PLHP errors cause program termination
ShowContinueError(state, | ||
format("Invalid {} = {}", state.dataIPShortCut->cAlphaFieldNames(9), state.dataIPShortCut->cAlphaArgs(9))); | ||
ErrorsFound = true; | ||
} |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Test severe error using FreeCoolingChiller_wWaterSideEconomizer:
** Severe ** GetConstCOPChillerInput: Chiller:ConstantCOP="MAIN CHILLER"
** ~~~ ** Invalid Thermosiphon Capacity Fraction Curve Name = THERMOCAPFRACCURVE2
** Fatal ** Errors found in processing input for Chiller:ConstantCOP
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
This is pretty impressive. High value addition for what appears to be like 2-3 hundred lines of code added. I'm going to play with this PR locally for a bit, but other than the repeated function, this is looking good from first inspection.
} else { | ||
return true; | ||
} | ||
} |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Yeah, this really shouldn't be repeated, right? Just add a reusable utility function somewhere accessible, add a few intent(inout)
arguments, and call it anywhere it's needed. UtilityFunctions probably isn't the right spot, but neither is GeneralRoutines. Or maybe one of them is the right spot? I dunno, and also this doesn't have to hold up this PR, but it is a bit odd to have copies of the same routine to maintain.
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
I wonder if such a routine would work in the plant component base class?
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
I did consider moving this to a common location but wasn't sure I knew what I was doing. The calculation inside this function would require unification of variables names in the chillers.
Real64 capFrac = this->ChillerPartLoadRatio * this->ChillerCyclingRatio; // Electric:EIR
Real64 capFrac = this->ChillerPartLoadRatio * this->ChillerCyclingRatio; // ReformulatedEIR
Real64 capFrac = this->partLoadRatio * this->cyclingRatio; // PlantChillers, Chiller:Electric
Real64 capFrac = this->partLoadRatio * this->cyclingRatio; // PlantLoopHeatPump:Cooling:EIR
Real64 capFrac = this->partLoadRatio * this->cyclingRatio; // Chiller:ConstantCOP
This still works fine with develop pulled in, let's just merge this in. Thanks @rraustad and @EnergyArchmage ! |