The IBEX concept of a block is similar to SECI, in that it is a relevant piece of information chosen by the scientist that will be displayed on the instrument dashboard and, if required, can be logged into the datafile.
In IBEX, a block is, to all intents and purposes, an alias to a process variable. For example, the block Chop1Freq
on LARMOR is defined to be the process variable IN:LARMOR:CS:SB:Chop1Freq
. It is much simpler to refer to a block than to refer to a process variable. Utilities like genie_python know about blocks, and you can use commands such as cset
to access Chop1Freq
. However, you can access blocks using the name IN:LARMOR:CS:SB:Chop1Freq
with any standard EPICS tool.
Process variables are defined in more detail on the Process Variables page.
An IBEX block may be in alarm as well as having a value. Alarms signify potential problems with the data
A disconnected status implies that the user interface cannot access the variable which has been requested.
Examples:
- The relevant IOC is not running - for example, the relevant ioc is not listed in the current configuration
- The IOC is running on another computer, and there is no network availability
These alarms appear with either a purple border or a solid purple background in the user interface.
An invalid alarm signifies that there was a problem acquiring this piece of data. Data marked with an invalid alarm should generally not be trusted.
Examples:
- The hardware has become unplugged or switched off
- The hardware replied in an unexpected way
- A setpoint has not been set (it will remain in an undefined state until set)
These alarms appear with a purple border in the user interface.
A major alarm signifies that there is a serious problem with the data being reported by a device. Data marked with an major alarm may require attention from an equipment expert.
Examples:
- A fault status is being reported by the hardware
- A chopper is not in the correct operation mode
Note: it is possible to set your own limits on a value going into major alarm - please ask the IBEX team if you would like help setting this up
These alarms appear with a red border in the user interface.
A minor alarm signifies a warning with the data being reported by a device. Data marked with a minor alarm should be checked, but if you are confident that the data is correct and within the expected ranges, can be ignored.
Examples:
- Motor parked on a limit switch
- Helium level in a cryostat falling low
Note: it is possible to set your own limits on a value going into minor alarm - please ask the IBEX team if you would like help setting this up
These alarms appear with an orange border in the user interface.