ZV2835RAC Knob Smart Dimmer

This describes the Z-Wave device ZV2835RAC, manufactured by Sunricher with the thing type UID of sunricher_zv2835rac_00_000. This version of the device is limited to firmware versions below 1.23

The device is in the category of Wall Switch, defining Any device attached to the wall that controls a binary status of something, for ex. a light switch.

ZV2835RAC product image

The ZV2835RAC supports routing. This allows the device to communicate using other routing enabled devices as intermediate routers. This device is also able to participate in the routing of data between other devices in the mesh network.

Overview

The knob smart dimmer is a Z-Wave device designed to work with various types of light sources. It may be connected to two-wire or three-wire configuration so it can operate with or without neutral lead. The dimmer can switch or dim connected light source either through Z-Wave devices or through the rotary knob directly. The smart dimmer is equipped with an algorithm of smart light source detection which makes configuration easier and ensures high compatibility of the device. It may be used as a switch with non-dimmable light sources (in 3-wire connection).

Main Features:

  • Advanced microprocessor control,
  • Implemented algorithm of smart light source detection,
  • Auto-adjustment of the appropriate control mode to connected load,
  • Active power and energy metering functionality,
  • Soft start function,
  • Memory of the last lighting level settings

It operates under the following loads:

  • Conventional incandescent and HV halogen light sources
  • ELV halogen lamps and dimmable LED bulbs (with electronic transformers)
  • MLV halogen lamps (with ferromagnetic transformers)
  • Dimmable LED bulbs
  • Dimmable compact fluorescent CFL tube lamps

It can be configured to use “Trailing edge” or “Leading edge” to control following load types:

  • "Trailing edge" for resistive loads
  • "Trailing edge" for capacitive loads
  • "Leading edge" for inductive loa

Inclusion Information

There are two methods to set the dimmer into inclusion mode:

  1. Repower on the dimmer, it will be set into inclusion mode automatically, and waiting to be included.
  2. Triple press reset button on the dimmer, it will set the dimmer into inclusion mode.

Exclusion Information

There are two exclusion methods:

Method 1: Exclusion from the primary controller/gateway as follows:

  1. Set the primary controller/gateway into exclusion mode (Please refer to your primary controllers manual on how to set your controller into exclusion).
  2. Triple press reset button, the dimmer will be set to exclusion mode, and waiting to be excluded, then the dimmer will be excluded from the network.

Method 2: Factory reset the dimmer will force it to be excluded from a network. Note: Factory reset is not recommended for exclusion, please use this procedure only if the primary controller/gateway is missing or otherwise inoperable.
Factory Reset: Press and hold down the reset button for over 10 seconds, the dimmer will be reset to factory defaults, the load brightness will be restored to 50% and will flash slowly.

General Usage Information

Channels

The following table summarises the channels available for the ZV2835RAC -:

Channel Name Channel ID Channel Type Category Item Type
Dimmer switch_dimmer switch_dimmer DimmableLight Dimmer
Scene Number scene_number scene_number Number
Electric meter (volts) meter_voltage meter_voltage Energy Number
Electric meter (amps) meter_current meter_current Energy Number
Electric meter (kWh) meter_kwh meter_kwh Energy Number
Electric meter (watts) meter_watts meter_watts Energy Number
Alarm (power) alarm_power alarm_power Energy Switch
Alarm (system) alarm_system alarm_system Switch

Dimmer

The brightness channel allows to control the brightness of a light. It is also possible to switch the light on and off.

The switch_dimmer channel is of type switch_dimmer and supports the Dimmer item and is in the DimmableLight category.

Scene Number

Triggers when a scene button is pressed.

The scene_number channel is of type scene_number and supports the Number item.

Electric meter (volts)

Indicates the instantaneous voltage.

The meter_voltage channel is of type meter_voltage and supports the Number item and is in the Energy category. This is a read only channel so will only be updated following state changes from the device.

Electric meter (amps)

Indicates the instantaneous current consumption.

The meter_current channel is of type meter_current and supports the Number item and is in the Energy category. This is a read only channel so will only be updated following state changes from the device.

Electric meter (kWh)

Indicates the energy consumption (kWh).

The meter_kwh channel is of type meter_kwh and supports the Number item and is in the Energy category. This is a read only channel so will only be updated following state changes from the device.

Electric meter (watts)

Indicates the instantaneous power consumption.

The meter_watts channel is of type meter_watts and supports the Number item and is in the Energy category. This is a read only channel so will only be updated following state changes from the device.

Alarm (power)

Indicates if a power alarm is triggered.

The alarm_power channel is of type alarm_power and supports the Switch item and is in the Energy category. This is a read only channel so will only be updated following state changes from the device.

The following state translation is provided for this channel to the Switch item type -:

Value Label
OFF OK
ON Alarm

Alarm (system)

Indicates if a system alarm is triggered.

The alarm_system channel is of type alarm_system and supports the Switch item. This is a read only channel so will only be updated following state changes from the device.

The following state translation is provided for this channel to the Switch item type -:

Value Label
OFF OK
ON Alarm

Device Configuration

The following table provides a summary of the 20 configuration parameters available in the ZV2835RAC. Detailed information on each parameter can be found in the sections below.

Param Name Description
2 Saving load state Saving load state before power failure
3 Basic report Send the basic report to the Lifeline when the load state changed
4 Default fade time Default fade time
5 Minimum brightness Minimum brightness
6 Maximum brightness Maximum brightness
7 MOSFET driving type MOSFET driving type
8 Step setting Step setting of the knob
9 Add and remove through switch Add and remove through switch
10 Load detection Load detection
11 Wiring type Wiring type
12 Load type Load type
13 Overcurrect Protection Overcurrect Protection
14 Power absolute threshold Power automatic report absolute threshold
15 Power percentage threshold Power automatic report percentage threshold
21 Power report cycle Power metering automatic report time cycle
22 Energy report cycle Energy metering automatic report time cycle
23 Voltage report cycle Voltage metering automatic report time cycle
24 Current report cycle Current metering automatic report time cycle
31 Dimming curve Dimming Curve
32 Startup brightness Startup brightness

Parameter 2: Saving load state

Saving load state before power failure Info: Saving load state before power failure 0 - shutoff load 1 - turn on load 2 - save load state before power failure The following option values may be configured -:

Value Description
0 Shutoff load
1 turn on load
2 Save load state

The manufacturer defined default value is 2 (Save load state ).

This parameter has the configuration ID config_2_1 and is of type INTEGER.

Parameter 3: Basic report

Send the basic report to the Lifeline when the load state changed Info: Enable/disable to send the basic report to the Lifeline when the load state changed(When value set as 1, re-power on the dimmer, it will send Basic report automatically) 0 - Disable to send Basic report 1 - Enable to send Basic report The following option values may be configured -:

Value Description
0 Disable Basic report
1 Enable Basic report

The manufacturer defined default value is 1 (Enable Basic report).

This parameter has the configuration ID config_3_1 and is of type INTEGER.

Parameter 4: Default fade time

Default fade time Default fade time (unit is second, this value has the same function as Duration of Multilevel) 0: Instantly 1-127: 1 to 127 seconds in 1 second resolution Values in the range 0 to 127 may be set.

The manufacturer defined default value is 1.

This parameter has the configuration ID config_4_1 and is of type INTEGER.

Parameter 5: Minimum brightness

Minimum brightness

Values in the range 0 to 50 may be set.

The manufacturer defined default value is 15.

This parameter has the configuration ID config_5_1 and is of type INTEGER.

Parameter 6: Maximum brightness

Maximum brightness

Values in the range 0 to 100 may be set.

The manufacturer defined default value is 100.

This parameter has the configuration ID config_6_1 and is of type INTEGER.

Parameter 7: MOSFET driving type

MOSFET driving type MOSFET driving type:

0 - trailing edge
1 - leading edge The following option values may be configured -:

Value Description
0 Trailing edge
1 Leading edge

The manufacturer defined default value is 0 (Trailing edge).

This parameter has the configuration ID config_7_1 and is of type INTEGER.

Parameter 8: Step setting

Step setting of the knob Setting step of the knob

Corresponding dimming stepping level for each rotation of the knob (a full dimming stepping level is 99) Valid value: 1-50 Values in the range 1 to 50 may be set.

The manufacturer defined default value is 5.

This parameter has the configuration ID config_8_1 and is of type INTEGER.

Parameter 9: Add and remove through switch

Add and remove through switch Added to and removed from a network through external switch (when enables this function, triple press the external switch within 1.5 seconds to be added to or removed from a network)

0 - disable
1 - enable The following option values may be configured -:

Value Description
0 Disable
1 Enable

The manufacturer defined default value is 0 (Disable).

This parameter has the configuration ID config_9_1 and is of type INTEGER.

Parameter 10: Load detection

Load detection Enable/disable to detect load after re-power on (detect load type, minimum brightness, maximum brightness)
0 - disable
1 - enable to detect every time after re-power on
2 - enable to detect only after first re-power on

Note: When the device does not belong to any network, load detection will be enabled every time after re-power on. When the device has already been added to a network, load detection will be disabled. The following option values may be configured -:

Value Description
0 Disable
1 Enable after each power on
2 Enable after first power on

The manufacturer defined default value is 0 (Disable).

This parameter has the configuration ID config_10_1 and is of type INTEGER.

Parameter 11: Wiring type

Wiring type Wiring type

0 - unknown
1 - 2 Wire With No Neutral
2 - 3 Wire With Neutral The following option values may be configured -:

Value Description
0 Unknown
1 2 Wire with no Neutral
2 3 Wire with Neutral

The manufacturer defined default value is 0 (Unknown).

This parameter has the configuration ID config_11_1 and is of type INTEGER. This is a read only parameter.

Parameter 12: Load type

Load type Load type

0 - unknown
1 - resistive
2 - inductive
3 - capacitive The following option values may be configured -:

Value Description
0 Unknown
1 Resistive
2 Inductive
3 Capacitive

The manufacturer defined default value is 0 (Unknown).

This parameter has the configuration ID config_12_1 and is of type INTEGER. This is a read only parameter.

Parameter 13: Overcurrect Protection

Overcurrect Protection Enable/disable over current protection (over 3.2A for 20 seconds continuously)

0 – disable
1 – enable The following option values may be configured -:

Value Description
0 Disable
1 Enable

The manufacturer defined default value is 1 (Enable).

This parameter has the configuration ID config_13_1 and is of type INTEGER.

Parameter 14: Power absolute threshold

Power automatic report absolute threshold Power automatic report absolute threshold, unit is W
When power changes above the absolute threshold, immediately report current power value Values in the range 0 to 600 may be set.

The manufacturer defined default value is 10.

This parameter has the configuration ID config_14_2 and is of type INTEGER.

Parameter 15: Power percentage threshold

Power automatic report percentage threshold Power automatic report percentage threshold, unit is %
When power changes above the percentage threshold, immediately report current power value Values in the range 0 to 100 may be set.

The manufacturer defined default value is 20.

This parameter has the configuration ID config_15_1 and is of type INTEGER.

Parameter 21: Power report cycle

Power metering automatic report time cycle Power metering automatic report time cycle, unit is second
Valid time cycle value: 5~2678400
Default is 600 seconds (10 minutes) Values in the range 5 to 2678400 may be set.

The manufacturer defined default value is 600.

This parameter has the configuration ID config_21_4 and is of type INTEGER.

Parameter 22: Energy report cycle

Energy metering automatic report time cycle Energy metering automatic report time cycle, unit is second

Valid time cycle value: 5~2678400

Default is 1800 seconds (30 minutes) Values in the range 5 to 2678400 may be set.

The manufacturer defined default value is 1800.

This parameter has the configuration ID config_22_4 and is of type INTEGER.

Parameter 23: Voltage report cycle

Voltage metering automatic report time cycle Voltage metering automatic report time cycle, unit is second

Valid time cycle value: 5~267840 Values in the range 5 to 2678400 may be set.

The manufacturer defined default value is 3600.

This parameter has the configuration ID config_23_4 and is of type INTEGER.

Parameter 24: Current report cycle

Current metering automatic report time cycle Current metering automatic report time cycle, unit is second

Valid time cycle value: 5~2678400 Values in the range 5 to 2678400 may be set.

The manufacturer defined default value is 3600.

This parameter has the configuration ID config_24_4 and is of type INTEGER.

Parameter 31: Dimming curve

Dimming Curve

The following option values may be configured -:

Value Description
0 Linear dimming
1 Logarithmic dimming

The manufacturer defined default value is 0 (Linear dimming).

This parameter has the configuration ID config_31_1 and is of type INTEGER.

Parameter 32: Startup brightness

Startup brightness Setting startup brightness of the load

Valid value: 0~99

Note: every time when turn on the load from OFF status, if the target brightness is lower than the startup brightness, the brightness will first go to the startup brightness value then fall down to the target brightness Values in the range 0 to 99 may be set.

The manufacturer defined default value is 0.

This parameter has the configuration ID config_32_1 and is of type INTEGER.

Association Groups

Association groups allow the device to send unsolicited reports to the controller, or other devices in the network. Using association groups can allow you to eliminate polling, providing instant feedback of a device state change without unnecessary network traffic.

The ZV2835RAC supports 2 association groups.

Group 1: Lifeline

The Lifeline association group reports device status to a hub and is not designed to control other devices directly. When using the Lineline group with a hub, in most cases, only the lifeline group will need to be configured and normally the hub will perform this automatically during the device initialisation.

Association group 1 supports 5 nodes.

Group 2: Launch 1

Association group 2 supports 5 nodes.

Technical Information

Endpoints

Endpoint 0

Command Class Comment
COMMAND_CLASS_NO_OPERATION_V1
COMMAND_CLASS_BASIC_V1
COMMAND_CLASS_SWITCH_MULTILEVEL_V3 Linked to BASIC
COMMAND_CLASS_SCENE_ACTIVATION_V1
COMMAND_CLASS_SCENE_ACTUATOR_CONF_V1
COMMAND_CLASS_METER_V3
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1
COMMAND_CLASS_DEVICE_RESET_LOCALLY_V1
COMMAND_CLASS_ZWAVEPLUS_INFO_V1
COMMAND_CLASS_CONFIGURATION_V1
COMMAND_CLASS_ALARM_V8
COMMAND_CLASS_MANUFACTURER_SPECIFIC_V1
COMMAND_CLASS_POWERLEVEL_V1
COMMAND_CLASS_FIRMWARE_UPDATE_MD_V1
COMMAND_CLASS_ASSOCIATION_V2
COMMAND_CLASS_VERSION_V2
COMMAND_CLASS_SECURITY_V1

Documentation Links