layout | title |
---|---|
documentation |
MH8-FC - ZWave |
{% include base.html %}
This describes the Z-Wave device MH8-FC, manufactured by McoHome Technology Co., Ltd with the thing type UID of mcohome_mh8fcplus_03_000
.
This version of the device is limited to firmware versions above 3.0
The device is in the category of HVAC, defining Air condition devices, Fans.
The MH8-FC supports routing. This allows the device to communicate using other routing enabled devices as intermediate routers. This device is also able to participate in the routing of data between other devices in the mesh network.
MCOHome Fan Coil Thermostat is a Z-Wave enabled device for indoor temperature control. It is mainly applied to a 4-pipe Fan coil system. It can read room temperature and local time, and automatically control fan speed based on the temperature difference. The device is of high reliability and practicability. This product can be included and operated in any Z-Wave network with other Z-Wave certified devices from any other manufacturers.
Features:
- Capacitive touch buttons
- Tempered glass panel, PC alloy enclosure
- Precise temperature calibration function
- Non-volatile Memory, working state saved even power failure
- Intelligent on/off control of 3-speed fan, electric (ball) valve or air-valve
- Easily steel frame back plate installatio
Specification
- Power Supply:AC85V~260V, 50/60HZ
- Resistive Load: ≤3A
- Self Consumption:< 1W
- Temperature Sensor: NTC 15K
- Display Accuracy: 0.1 ℃
- Working Environment:0~55℃; <95% RH(Non-condensation)
- Temperature Setting:5~35 ℃(Adjustable)
- Dimension:86* 86*42mm
- Hole Pitch:60-65mm(86 Standard junction box)
- Z-Wave Frequency: 868.42MHz (EU)
Safety Information
To protect yourself and others from danger and to protect the device from damage, please read the safety information before using it.
Including of Z-Wave network
Under the shutdown state, press & hold "Down Arrow" to enter interface for inclusion or exclusion of Z-Wave network.
Before device included into network, “- - -” will display on the screen. Then press once "Down Arrow", device will enter learning mode to get a node ID. If inclusion is success, a node ID will display on the screen in a few seconds.
A node ID can always inform us whether the device is in the network or not.
Excluding of Z-Wave network
Under the shutdown state, press & hold "Down Arrow" to enter interface for inclusion or exclusion of Z-Wave network.
Before device included into network, “- - -” will display on the screen. Then press once "Down Arrow", device will enter learning mode to get a node ID. If inclusion is success, a node ID will display on the screen in a few seconds.
A node ID can always inform us whether the device is in the network or not.
The following table summarises the channels available for the MH8-FC -:
Channel Name | Channel ID | Channel Type | Category | Item Type |
---|---|---|---|---|
Sensor (temperature) | sensor_temperature | sensor_temperature | Temperature | Number:Temperature |
Thermostat mode | thermostat_mode | thermostat_mode | Temperature | Number |
Operating State | thermostat_state | thermostat_state | Temperature | Number |
Setpoint (cooling) | thermostat_setpoint | thermostat_setpoint | Heating | Number:Temperature |
Setpoint (heating) | thermostat_setpoint | thermostat_setpoint | Heating | Number:Temperature |
Thermostat fan mode | thermostat_fanmode | thermostat_fanmode | ||
Thermostat fan state | thermostat_fanstate | thermostat_fanstate |
Indicates the current temperature.
The sensor_temperature
channel is of type sensor_temperature
and supports the Number:Temperature
item and is in the Temperature
category.
Sets the thermostat.
The thermostat_mode
channel is of type thermostat_mode
and supports the Number
item and is in the Temperature
category.
The following state translation is provided for this channel to the Number
item type -:
Value | Label |
---|---|
0 | Off |
1 | Heat |
2 | Cool |
3 | Auto |
4 | Aux Heat |
5 | Resume |
6 | Fan Only |
7 | Furnace |
8 | Dry Air |
9 | Moist Air |
10 | Auto Changeover |
11 | Heat Economy |
12 | Cool Economy |
13 | Away |
Sets the thermostat operating state.
The thermostat_state
channel is of type thermostat_state
and supports the Number
item and is in the Temperature
category.
The following state translation is provided for this channel to the Number
item type -:
Value | Label |
---|---|
0 | Idle |
1 | Heating |
2 | Cooling |
3 | Fan Only |
4 | Pending Heat |
5 | Pending Cool |
6 | Vent / Economiser |
Sets the thermostat setpoint.
The thermostat_setpoint
channel is of type thermostat_setpoint
and supports the Number:Temperature
item and is in the Heating
category.
Sets the thermostat setpoint.
The thermostat_setpoint
channel is of type thermostat_setpoint
and supports the Number:Temperature
item and is in the Heating
category.
Channel type information on this channel is not found.
Channel type information on this channel is not found.
The following table provides a summary of the 5 configuration parameters available in the MH8-FC. Detailed information on each parameter can be found in the sections below.
Param | Name | Description |
---|---|---|
1 | Temperature Unit Setting | Temperature Unit Setting. 0 = C, 1 = F |
2 | Upload Temperature Automatically | Upload Temperature Automatically |
3 | Upload temperature difference | Upload temperature difference |
4 | Upload time interval | Upload time interval in seconds |
255 | Factory Setting | Factory Setting |
Temperature Unit Setting. 0 = C, 1 = F
The following option values may be configured -:
Value | Description |
---|---|
0 | Celcius |
1 | Fahrenheit |
The manufacturer defined default value is 0
(Celcius).
This parameter has the configuration ID config_1_1
and is of type INTEGER
.
Upload Temperature Automatically
The following option values may be configured -:
Value | Description |
---|---|
0 | Off |
1 | Upload the difference value only |
2 | Timing upload mode only |
3 | Upload the difference + timing upload mode |
The manufacturer defined default value is 3
(Upload the difference + timing upload mode).
This parameter has the configuration ID config_2_1
and is of type INTEGER
.
Upload temperature difference Base on 0.1C unit. 5 by default. 5 * 0.1C = 0.5C, 0x0003 to 0x03E8 Values in the range 3 to 1000 may be set.
The manufacturer defined default value is 5
.
This parameter has the configuration ID config_3_2
and is of type INTEGER
.
Upload time interval in seconds Base is 1s unit. It is suggested to be set above 30s, 0x000A to 0xFFFF Values in the range 10 to 65535 may be set.
The manufacturer defined default value is 30
.
This parameter has the configuration ID config_4_2
and is of type INTEGER
.
Factory Setting 0x55 Restore the factory setting (write only)
Parameters setting back to default value, association groups deleted Values in the range 85 to 85 may be set.
The manufacturer defined default value is 85
.
This parameter has the configuration ID config_255_1_wo
and is of type INTEGER
.
This is a write only parameter.
Association groups allow the device to send unsolicited reports to the controller, or other devices in the network. Using association groups can allow you to eliminate polling, providing instant feedback of a device state change without unnecessary network traffic.
The MH8-FC supports 1 association group.
The Lifeline association group reports device status to a hub and is not designed to control other devices directly. When using the Lineline group with a hub, in most cases, only the lifeline group will need to be configured and normally the hub will perform this automatically during the device initialisation. For sending temperature, working mode, etc. notifications
Association group 1 supports 1 node.
Command Class | Comment |
---|---|
COMMAND_CLASS_NO_OPERATION_V1 | |
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_SENSOR_MULTILEVEL_V5 | |
COMMAND_CLASS_THERMOSTAT_MODE_V1 | |
COMMAND_CLASS_THERMOSTAT_OPERATING_STATE_V1 | |
COMMAND_CLASS_THERMOSTAT_SETPOINT_V1 | |
COMMAND_CLASS_THERMOSTAT_FAN_MODE_V1 | |
COMMAND_CLASS_THERMOSTAT_FAN_STATE_V1 | |
COMMAND_CLASS_CONFIGURATION_V1 | |
COMMAND_CLASS_MANUFACTURER_SPECIFIC_V1 | |
COMMAND_CLASS_ASSOCIATION_V1 | |
COMMAND_CLASS_VERSION_V1 |
Did you spot an error in the above definition or want to improve the content? You can contribute to the database here.