-
Notifications
You must be signed in to change notification settings - Fork 397
New issue
Have a question about this project? Sign up for a free GitHub account to open an issue and contact its maintainers and the community.
By clicking “Sign up for GitHub”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.
Already on GitHub? Sign in to your account
Outdoor Air Summary report improvements #5298
Comments
@JasonGlazer It may be too late to tackle this one before the feature freeze, but even a partial addition of OA volume flow rates at standard density with a total row might be helpful at this point. Or perhaps we build a custom monthly table as a starting point. |
Any updates on this issue? This would be very helpful for LEED Reviewers. The total minimum OA for the building needs to be compared between the Baseline and Proposed Case models. |
Another improvement here is that the Controller:OutdoorAir component sizing summary only shows values if the min/mas were autosized. If the user enters a hard value the table is empty. The hard value should be reported as well when not autosized |
I would suggest including design (not including the economizer mode where OA may equal SA) and minimum (to check that area ventilation requirement is modeled correctly if DCV is included) occupied ventilation by system (both zone level and air handlers) and a total for the building in the Outdoor Air Summary report. Alternatively, if it would make more sense, this information could be included in a new report. You could label the new report as ASHRAE 62 Ventilation Summary, Mechanical Ventilation Summary, etc. I used to be a LEED Reviewer and this information would have been very helpful to me. |
Thinking about tabular reports (hence forgetting about tables of hour versus month (weekends v weekends too) showing OA numbers), I would say that two metrics would be useful:
That would help see whether the deviation in absolute numbers are off because of economizer or not. *It does somewhat follow what @mjwitte said on the issue itself, with a slight difference, Mike's solution of tracking OA if econ wasn't running is probably harder to implement Quick two cents really... |
Helpdesk ticket 10907 (and others)
Users often find it difficult to compare the outdoor air delivered for proposed vs baseline simulations. The logical place to look is the Outdoor Air Summary Report and the component sizing report.
The component sizing report shows the minimum outdoor air flow rates for Controller:OutdoorAir objects that have autosized OA flow rates, but there is no building total. But this would only cover air handlers, not zone equipment. OA flow rates show up in some other tables as well, but again, no building totals.
The Outdoor Air Summary report has average and minimum OA flow rates during occupied hours listed by zone, reported as ACH. I would be helpful to add flow in CFM or m3/s to these tables, and to add a total row for the entire building.
Economizers can cloud the issue as well. Is it useful to report what the minimum flows would be if the economizer was not operating?
Before tackling this, some users and LEED reviewers should be consulted to find out exactly what type of output would be useful for showing that the "two alternatives are delivering the same amount of outside air".
The text was updated successfully, but these errors were encountered: