PID Module Should Probably Reinit IP After Transitioning From Safe-State or Init #2

Open
Beazurt opened this issue Aug 7, 2015 · 0 comments
Labels

Comments

@Beazurt
Copy link

Beazurt commented Aug 7, 2015

The 'reinitialize? (F)' input of the main PID is currently unwired. I believe this means that the integrated error will remain after going to safe state or reinitializing the plugin between runs. This could cause an unexpected jump after those transitions.